Los Angeles, California building permit
25041-10000-27487
PC Info Complete
2500 S NAVY WAY — all permits at this address
NEW DATA CENTER WITH REDUNDANT (N+1) EQUIPMENTONE SET OF UPS,TRANSFORMER, PANEL WILL BE ON NORMAL POWER AND AREDUNDANT SET WILL BE ON EMERGENCY POWER.1. TWO 200KVA 120/208V, 3, UPS UNITS2. TWO 225KVA 480V-120/208V, 3, 4W TRANSFORMER (HARMONIC RATED)3. TWO 600A, 120/208V, 3,4W, 60 SPACE PANELBOARD4. (14) 60A 208V RECEPTACLES TO FEED PDU'S IN RACKS FROM EACH PANEL.5. REMODEL WITH NEW LIGHTING AND CONTROLS.6. POWER FOR 2 NEW CRAC UNITS IN DATA CENTER.7. POWER FOR 2 NEW CONDENSING UNITS ON THE ROOF.
Status date2025-07-21
JurisdictionLos Angeles, California
SourceLos Angeles Open Data (LADBS)
Data freshnessOfficial city open data (LADBS)