The following revisions have been made to the plans:1. Interconnection method revised to 120% rule as this main panel is rated for 125A busbar and has a 100A Main Breaker. New 200A Load Center installed for single point interconnection where existing pv breaker and new backup interface feeder breaker will be installed. The Non Backup loads panel has been removed from the planset since these non backup loads will now remain in the main service panel with the new interconnection being 120%.Changes
Status date2025-12-02
JurisdictionLos Angeles, California
SourceLos Angeles Open Data (LADBS)
Data freshnessOfficial city open data (LADBS)