[ePlan] (PC ONLY) Changes to approved set. Revision of meter main disconnect switch fuses from 500A to 600A. Retro-fill existing 4000A pressure switch and fuse for 4000A busduct with new 4000A CB. SQD short circuit evaluation and breaker settings have been provided, as well as the SQD busway shop drawings PC for clouded changes only.